8-4
OPTIONAL DESK CONTROL UNIT
L1 POWER SUPPLY
L2 POWER SUPPLY
24 VOLTS
FROM DESK
TO PTAC
SELECTOR
SWITCH
DESK CONTROL RELAY (N.C.)
L1 POWER SUPPLY
L2 POWER SUPPLY
24 VOLTS
FROM DESK
TO PTAC
SELECTOR
SWITCH
DESK CONTROL RELAY (N.C.)
The desk control unit allows the air conditioner
to be turned off and on from a remote location.
The unit consists of a pair of switches that are
controlled by a 24-volt relay.
The main power supply is wired in series through
the relay contacts. When the desk control
switch is open, the 24-volt supply is removed
from the relay coil, the contacts are closed, and
the air conditioner will operate.
When the desk control switch is closed, the 24-
volt supply is applied to the relay coil,the con-
tacts open, and the air conditioner will not
operate.The air conditioner will not run as long
as the 24 volts is present at the desk control
unit.