5-2
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
MODE (SYSTEM) SWITCH
HEAT ANTICIPATOR
Refer to page 4-2 for the procedure for servic-
ing the mode (system) switch.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the wires from the mode switch
terminals.
3.
Set the ohmmeter to the R x 1 scale.
4.
To check the switch contact operation,
touch the ohmmeter test leads to the switch
terminals shown in the following charts:
Refer to page 4-2 for the procedure for servic-
ing the heat anticipator.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the heat anticipator wires from
the mode switch terminals.
3.
Set the ohmmeter to the R x 10K scale.
4.
Touch the ohmmeter test leads to the
ends of the orange heat anticipator wires.
The meter should indicate approximately
56 K
Ω
.
SWITCH POSITION
CONTACTS MADE
OFF
NONE
LOW COOL
L1 - 2
5 - 3
4 - 6
L - 9
COM - L2
HIGH COOL
L1 - 2
5 - 3
4 - 6
H - 9
COM - L2
SWITCH CONTINUITY
FAN ONLY
8 - H
COM - L2
L1 - 8
HIGH HEAT
L1 - 2
5 - 1
7 - 6
H - 9
COM - L2
LOW HEAT
L1 - 2
5 - 1
7 - 6
L - 9
COM - L2
SWITCH POSITION
CONTACTS MADE
OFF
NONE
SWITCH CONTINUITY
Summary of Contents for ATE0743RPP
Page 20: ...2 12 NOTES ...
Page 30: ...3 10 NOTES ...
Page 71: ...7 5 WIRING DIAGRAMS DIAGRAM 1 ...
Page 72: ...7 6 DIAGRAM 3 DIAGRAM 2 ...
Page 73: ...7 7 DIAGRAM 4 DIAGRAM 5 ...
Page 74: ...7 8 DIAGRAM 7 DIAGRAM 6 ...
Page 75: ...7 9 DIAGRAM 8 ...
Page 84: ...7 18 NOTES ...
Page 90: ...8 6 NOTES ...
Page 92: ...CORPORATION ...