Table
The table results show the average harmonic readings and the maximum
individual smoothed harmonic readings compared to the limits.
In the example above, the results for harmonic 5 show that the average
result has exceeded limit 1 but not limit 2 and that the maximum reading
has not exceeded limit 2 resulting in a FAIL for harmonic 5. See the
reference information for more details.