29
Enrolling devices
For a temperature zone to be able to be managed from a remote location via the GSM-BUS Communicator
01942, it is first necessary to enable remote access, using the specific menu of the control panel (refer to the
relevant instructions manual)
It is possible to perform the temperature zone enrolment procedure by following an automatic procedure or a
manual procedure
12.3.1 Automatic enrolment of the control panel temperature zones.
This procedure makes a sequential association of the temperature zones that the specified control panel makes
accessible from a remote location
The procedure involves the following operations:
1 The first available “thermostat” (C1,, C40) of the communicator is associated with the first enabled tem-
perature zone of the specified control panel
2 The second available “thermostat” of the communicator is associated with the second enabled tempera-
ture zone of the control panel
and so on for all the temperature zones of the control panel or of the available “thermostats” in the communi-
cator
Therefore, if 40 temperature zones have already been enrolled, another automatic enrolment command will have
no effect
Example: If you want to enrol temperature zones 1, 2, 3, 4 of the control panel associated with the SYS1 sys-
tem and the temperature zones 1, 2, 3, 4 of the comfort control panel associated with the SYS2 system using
the automatic procedure, if other temperature zones have not previously been enrolled, you will obtain the fol-
lowing association:
C1
Temperature zone 1 of the control panel 1 (SYS1)
C2
Temperature zone 2 of the control panel 1 (SYS1)
C3
Temperature zone 3 of the control panel 1 (SYS1)
C4
Temperature zone 4 of the control panel 1 (SYS1)
C5
Temperature zone 1 of the control panel 2 (SYS2)
C6
Temperature zone 2 of the control panel 2 (SYS2)
C7
Temperature zone 3 of the control panel 2 (SYS2)
C8
Temperature zone 4 of the control panel 2 (SYS2)
The procedure can be activated either with an SMS text message or via the EasyTool
•
Send an SMS message in the form of
<user code>.SYS<n>.AAC
where
<n>
is the number identifying the system associated with the control panel of the temperature zones
to enrol
This command does not require an SMS confirmation message.