Setting the maximum heat pump flow
temperature.
!
Please note
Avoiding device damage.
Never
set the maximum flow
temperature higher than 55
°C.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heat pump
"
&
"max. flow temp."
(
1
/
!
)
Standard setting
55 °C
Setting range
25 to 60 °C
Minimum return temperature
Not the heat pump but the electric
heater is started when the actual tem-
perature falls below the minimum
return temperature on the secondary
side.
The electric heater stays ON until the
minimum return temperature has
been reached.
Note
The compressor wear will increase
through more frequent low pressure
shutdowns, if the minimum return tem-
perature is set too low.
Setting the minimum return tempera-
ture too high increases the proportion
of electric heating, resulting in
reduced efficiency. This problem
occurs primarily when heating up a
cold building.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heat pump
"
&
"Min. return temp."
(
1
/
!
)
Standard setting
5 °C
Setting range
1 to 40 °C
Maximum flow temperature
84
Heat pump control settings
55
92
901
GB