Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"
max. flow correction
" (
0
/
=
)
Standard setting
10.0 K
Setting range
0.1 to 10.0 K
Room temperature control
A room temperature-dependent con-
trol is possible subject to a room tem-
perature sensor being installed and
enabled (see page 105). This function
must be enabled for this.
Note
The heating curve level and slope can
no longer be adjusted (parameter of
the weather-compensated control
unit), if you have selected "
Yes
" for
room temperature control.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Room control"
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Setting the slope and level of the heating curve
Operating instructions
Vitocal 300, section "Modifying
the heating characteristics of
the heating circuits"
Integral room temperature controller
Prerequisite: "
Room temperature
controller
" set to "
Yes
" (see
page 107).
Integral part of the room temperature
control circuit. A high value results in
a rapid response.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Integr. room reg."
(
[
/
]
)
Maximum flow temperature correction
(cont.)
107
Heating circuit control settings
55
92
901
GB
Service
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...