Setting parameters
Setting range
Standard
setting
Commission-
ing
Buffer cylinder pro-
gram
7-day program
OFF
Fixed temperature
1 to 60 °C
50 °C
Temperature hyster-
esis
2 to 20 K
5 K
Max. temperature
1 to 70 °C
60 °C
Stop optimisation
No/Yes
No
Excess reaction
0 to 2
*
1
2
2. Temperature sensor
No/Yes
No
"Natural cooling"
Natural cooling circuit
No/Yes
No
Room temperature
10 to 30 °C
20 °C
Room temperature
hysteresis
0.5 to 10.0 K
1.0 K
Room temperature
control
No/Yes
Yes
Room temperature
hook-up slope
0 to 50
10
Level, cooling curve
-15 to 40
0
Slope, cooling curve
0.0 to 3.5
1.2
Integral room tempera-
ture controller
5 to 1000
100
Minimum flow tem-
perature
1 to 30 °C
10 °C
Natural cooling with
mixer
No/Yes
No
Cooling mixer runtime
0:05 to 4:15 min
0:10 minutes
Mixer active zone
2.0 to 40 K
4.0 K
Mixer dead zone
0.5 to 3.0 K
1.0 K
External heat source
External heat source
No/Yes
No
Priority ext. heat
source
No/Yes
Yes
Temperature limit for
operation
-50 to +50 °C
10 °C
Threshold ext. heat
source
10 to 3000
300
Delay ext. heat source
0:00 to 5:00 h
0:30 h
Reports of control parameters
(cont.)
147
Commissioning/service reports
55
92
901
GB
Service
*1
0: No reaction; 1: Draw-off only in case of critical excess; 2: Always draw-off.
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...