Vitocal 300
Type
WWC 104
WWC 106 WWC 108
WWC 110
Heat pump perfor-
mance data
Operating point
*
1
W10/W35
W10/W35
W10/W35
W10/W35
Rated heating output
kW
6.3
8.4
10.9
14.2
Refrigerating capacity
kW
5.15
6.90
9.00
11.70
Power consumption
kW
1.15
1.50
1.90
2.50
Coefficient of perfor-
mance
∊
(COP)
during heating opera-
tion
5.48
5.60
5.74
5.68
Electric heater
Heat output (stepped)
kW
stepped 3/6/9
Max. output
Vitocal 300
kW
15.3
17.4
19.9
23.2
Groundwater
(pri-
mary)
Circulation pump
Type
Wilo TOP-S 25/7
Content
Litre
1.7
2.3
2.8
3.7
Min. throughput
*
2
l/h
1150
1600
2100
2700
Max. external pressure
drop
mbar
540
520
490
460
Max. inlet temperature
°C
25
25
25
25
Min. inlet temperature
&
at min. throughput
°C
7.5
7.5
7.5
7.5
&
at min. throughput
+40%
°C
6.5
6.5
6.5
6.5
Heating water
(sec-
ondary)
Circulation pump
Type
Wilo RS 25/7-3
Content
Litre
1.4
1.6
2.2
2.7
Min. throughput
*
2
l/h
440
580
730
1000
Max. external pressure
drop
mbar
530
520
510
500
Max. flow temperature
°C
55
55
55
55
Refrigerant circuit
Refrigerant
R 407 C
Fill volume
kg
1.7
1.9
2.2
2.6
Compressor
Type
Hermetically sealed scroll compressor
Electrical values
Specification type WWC
151
Specification type WWC
55
92
901
GB
Service
*1
Operating point to EN 255: W 10 = Groundwater inlet temperature 10 °C/W 35 = heating
water output temperature 35 °C.
*2
Always safeguard the min. throughput.
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...