The selected set room temperature is
20 °C, the value entered under "
Heat.
limit
<
T room
" is 4.0 K.
Central heating commences if the
average outside temperature drops
below 16 °C (heating limit tempera-
ture).
If the outside temperature exceeds
18 °C, central heating is adjusted
because of the specified hysteresis of
2 K.
A
Set room temperature
B
Outside temperature
C
Selected value "
Heat. limit
<
T
room
"
D
Heating OFF
E
Heating ON
Access
&
"
System settings
"
&
"
Program
"
&
"
System definition
"
&
"Heat. limit
<
T room"
(
1
/
!
)
Standard setting
4 K
Setting range
0 to 20 K
Temperature limit for reduced temperature mode
The "reduced" temperature mode
(see operating instructions, "setting
switching times") will no longer be
used, if the average outside tempera-
ture falls
below
the temperature limit
selected here. The device heats up to
the temperature selected for "stan-
dard" mode.
Operation will continue in accordance
with the selected switching times, if
the average outside temperature
stays
above
this temperature limit.
Note
The standard setting of
–
30 °C means
that this function is disabled.
Access
&
"
System settings
"
&
"
Program
"
&
"
System definition
"
&
"Red. mode T thresh
’
d"
(
1
/
!
)
Heating limit
<
T room (heating limit temperature)
(cont.)
81
System definition control settings
55
92
901
GB
Service
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...