Setting of the time required by the ser-
vomotor of the cooling mixer for a
complete
changeover from one oper-
ating state into another (90 degree
movement).
Runtimes that are too short, can lead
to the cooling mixer "Cycling".
Access
&
"
System settings
"
&
"
Program
"
&
"
Natural Cooling
"
&
"Cooling mixer runtime"
(
m
/
l
)
Standard setting
0:10 minutes
Setting range
0:05 to
4:15 min
Mixer active zone/dead zone
For function description see
page 110.
Access
&
"
System settings
"
&
"
Program
"
&
"
Natural cooling
"
&
"Heat mixer scan band "
(
%
/
5
)
or
"Heat mix non-op band "
(
=
/
0
)
Standard setting
Setting range
"
Heat mixer scan band
"
4.0 K
2.0 to 40 K
"
Heat mix non-op band
"
1.0 K
0.5 to 3.0 K
Cooling mixer runtime
121
Control settings "natural cooling"
55
92
901
GB
Service