This setting determines whether the
heat pump plus the electric heater are
to be used for drying the building.
Set this function to "
NO
" if the heat
pump is not ready for use, for example
because the primary heat pump circuit
is not yet completed at the time the
building is to be dried out.
Note
When using a heat pump for drying
buildings there is a risk that the pri-
mary side will become overloaded.
This can lead to
permanent
damage
to the ground probes/collectors.
Access
&
"
System settings
"
&
"
Program
"
&
"
Internal hydraulic
"
&
"HP for building dry."
("YES"/"NO")
Standard setting
NO
Setting range
YES/NO
Time for drying buildings
Setting of the number of days that the
system should provide heat for drying
buildings.
Heating is provided at the maximum
flow temperature of the heating circuit
(see page 103).
The "
0
" setting switches this function
OFF.
The remaining days for drying build-
ings will be shown on the display
when the programming unit flap is
closed.
Note
If the "
Screed function
" (see
page 109) has been activated, no
intervention must occur here.
The settings under "
Screed function
"
are directly related to this setting. The
settings of both functions influence
each other.
Access
&
"
System settings
"
&
"
Program
"
&
"
Internal hydraulic
"
&
"Time building drying"
(
j
/
k
)
Standard setting
0
(function
"
OFF
")
Setting range
0 to 30 days
Heat pump for drying buildings
93
Internal hydraulics control settings
55
92
901
GB
Service
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...