5.
Terminate the test program with
"
BACK
".
Checking the primary and secondary pumps
1.
Start the test program:
Menu item
&
"
System settings
"
&
"
Tech. service level
"
&
"
Commissioning
"
&
"
Primary pump
"
Note
The compressor will start automati-
cally after expiry of the 250 s long
test.
The time elapsed since the start of
the test program is shown in the top
r.h. corner of the display. Further-
more, the status of all components
that are part of the test procedure
is displayed.
2.
Checking the circulation on the pri-
mary side (brine circuit)
&
The primary inlet (display "
Pri-
mary input
") and outlet (display
"
Primary off
") must show identi-
cal, low temperatures.
&
The pump casing of the primary
cooling circuit pump must not
heat up (check by touching the
casing).
Otherwise
&
Vent the primary circuit.
&
Check the pump connections.
&
Select a different pump stage or
use an external pump.
3.
Start the compressor by
pressing "
ON
".
4.
Check the primary pump:
Determine the temperature differ-
ential
Δ
T between the primary inlet
(display "
Primary input
") and out-
let (display "
Primary off
").
Set values
Δ
T:
&
3 to 5 K at 35 °C for "
Secondary
flow
" and 10 °C for "
Primary
input
"
&
2 to 4 K at 35 °C for "
Secondary
flow
" and 0 °C for "
Primary
input
"
5.
Check the secondary pump:
Determine the temperature differ-
ential
Δ
T between the "
Secondary
flow
" and the "
Secondary return
".
Set values
Δ
T:
&
4 to 13 K at 35 °C for "
Secondary
flow
" and 10 °C for "
Primary
input
"
&
3 to 10 K at 35 °C for "
Secondary
flow
" and 0 °C for "
Primary
input
"
6.
Record the results in the service
report from page 143.
If the set values are not achieved:
&
Vent the primary circuit.
&
Vent the secondary circuit.
&
Check the pump connections.
&
Select a different pump stage or
use a larger pump.
Further details regarding the individual steps
(cont.)
50
Commissioning, inspection, maintenance
55
92
901
GB
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...