Coordination of the heat drawn off in
the secondary circuit when the heat
pump produces an excess of heat or
the heat drawn by the secondary cir-
cuit is suddenly choked off.
Settings:
0 No heat drawn off
1 Heat will be drawn off only in case
of a critical excess, i.e. if critical
temperatures were reached in the
heat pump circuit or the minimum
heat pump runtime has not yet
been reached.
2 Heat will be drawn off, even if the
excess heat being created is not
critical for the heat pump
Access
&
"
System settings
"
&
"
Program
"
&
"
DHW
"
&
"Reaction overplus"
(
l
/
m
)
Standard setting
2
Setting range
0 to 2
DHW priority
When DHW priority has been
enabled, the DHW cylinder will be
heated, until the selected DHW tem-
perature (see operating instructions
Vitocal 300) has been reached or the
period selected under "
max. DHW
runtime
" (see page 99) has expired.
Only then will the heating circuit be
supplied with heat.
Access
&
"
System settings
"
&
"
Program
"
&
"
DHW
"
&
"DHW priority"
("
YES
"/"
NO
")
Standard setting
YES
Setting range
YES/NO
Excess reaction
99
DHW control unit settings
55
92
901
GB
Service
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...