Setting parameters
Setting range
Standard
setting
Commission-
ing
DHW program tem-
perature
7-day program
OFF
DHW circulation pump
program
7-day program
OFF
Operating mode
0 to 6
*
1
4
DHW cylinder max.
20 to 80 °C
60 °C
Hysteresis, DHW elec-
tric heating
2 to 30 K
10 K
Hysteresis
1 to 10 K
7 K
Start optimisation
No/Yes
Yes
Stop optimisation
No/Yes
Yes
Auxiliary DHW func-
tion
No/Yes
No
Set DHW temperature
2
10 to 70 °C
60 °C
DHW temperature
sensor 2, bottom
No/Yes
No
Excess reaction
0 to 2
*
2
2
DHW with electric
power
No/Yes
Yes
DHW priority
No/Yes
Yes
Max. DHW runtime
00:10 to 24:00 h
04:00 h
Max. DHW interruption 00:10 to 24:00 h
01:30 h
Temperature rise per
hour
0 to 100 K/h
26 K/h
Electric heater rod
No/Yes
No
Heating circuit
Standard temperature
10 to 30 °C
20 °C
Reduced temperature
10 to 30 °C
14 °C
Temp. program HC
7-day program
OFF
Operating mode
0 to 7
*
3
4
Max. flow temperature
10 to 70 °C
40 °C
Min. flow temperature
1 to 30 °C
10 °C
DHW during party
mode
No/Yes
Yes
Reports of control parameters
(cont.)
145
Commissioning/service reports
55
92
901
GB
Service
*1
0: Standby; 1: Reduced; 2: Standard; 3: Fixed value; 4: Rotary selector; 5: External;
6: Switching times.
*2
0: no reaction; 1: Draw-off only in case of critical excess; 2: Always draw-off.
*3
0: Standby; 1: Reduced; 2: Standard; 3: Fixed value (at max. flow temperature); 4: Rotary
selector; 5: External (no function); 6: Switching times; 7: Remote control.
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...