Heating circuit 1/2
"
&
"Reaction overplus "
(
l
/
m
)
Standard setting
2
Setting range
0 to 2
Room temperature sensor
Any installed room temperature sen-
sor must be enabled for the corre-
sponding heating circuit.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Room temp. sensor "
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Slope, room temperature hook-up
The slope for room temperature hook-
up can be selected, subject to a room
temperature sensor being installed
and activated (see page 105) and
room temperature hook-up being
enabled (see page 105).
The higher the selected value, the
greater the influence of the room tem-
perature.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Slope Room hook-up"
(
l
/
m
)
Standard setting
10
Setting range
0 to 10
Room temperature hook-up
Prerequisites: Room temperature
sensor installed and enabled (see
page 105).
This setting determines, when the
room temperature hook-up should be
enabled in addition to the weather-
compensated control.
Settings:
0
No room temperature hook-up
1
Room temperature hook-up only in reduced mode
Excess reaction
(cont.)
105
Heating circuit control settings
55
92
901
GB
Service
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...