Setting parameters
Setting range
Standard
setting
Commission-
ing
Excess reaction
0 to 2
*
1
2
Room temperature
sensor
No/Yes
No
Slope, room tempera-
ture hook-up
0 to 10
10
Room temperature
hook-up
0 to 3
*
2
0
Start optimisation
No/Yes
No
Max. flow temperature
correction
0.1 to 10.0 K
10.0 K
Room temperature
control
No/Yes
No
Heating curve level
-15 to 40 K
0 K
Heating curve slope
0.0 to 3.5
0.6
Integral room tempera-
ture controller
5 to 1000
100
Room temperature ex-
cess
0 to 20 K
5 K
Flow T excess
-10 to 40 K
0 K
Mixer runtime
0:05 to 4:15 min
0:10 minutes
Screed function
0 to 15
0 (passive)
Mixer active zone
2 to 40 K
4 K
Mixer dead zone
0.5 to 3 K
1 K
Natural cooling
No/Yes
No
Cooling limit > T room
2 to 20 K
4 K
Level, cooling curve
-15 to 40
0
Slope, cooling curve
0.0 to 3.5
1.2
Natural cooling with
mixer
No/Yes
No
Active zone natural
cooling
–
mixer
2 to 40 K
4 K
Dead zone natural
cooling
–
mixer
0.5 to 3 K
1 K
Cooling mixer runtime
0:05 to 4:15 min
0:10 minutes
DHW buffer cylinder
Buffer cylinder
No/Yes
No
Reports of control parameters
(cont.)
146
Commissioning/service reports
55
92
901
GB
*1
0: no reaction; 1: Draw-off only in case of critical excess; 2: Always draw-off.
*2
0: never; 1: only reduced mode; 2: only standard mode; 3: in reduced and in standard
mode.
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...