For function, see page 110.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"NC mixer scan band "
(
%
/
5
)
or
"NC mixer dead zone"
(
=
/
0
)
Standard setting
Setting range
"
NC mixer active zone
"
4.0 K
2.0 to 40 K
"
NC mixer dead zone
"
1.0 K
0.5 to 3.0 K
Cooling mixer runtime
Setting of the time required by the ser-
vomotor of the cooling mixer for a
complete
changeover from one oper-
ating state into another (90 degree
movement).
Runtimes that are too short, can lead
to the cooling mixer "Cycling".
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Op. time cool. mixer "
(
m
/
l
)
Standard setting
0:10 min
Setting range
0:05 to
4:15 min
Active zone/dead zone natural cooling mixer
114
Heating circuit control settings
55
92
901
GB