A
Mixer permanently closed
B
Mixer closes (modulating)
C
Mixer motor at zero volt
D
Mixer opens
E
Mixer permanently open
T
V
Flow temperature
T
Vs
Set flow temperature
Δ
T
Vh
Active zone
Δ
T
Vt
Dead zone
t
Time
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Heat mixer scan band"
(
%
/
5
)
or
"Heat mix non-op band"
(
=
/
0
)
Standard setting
Setting range
"
Heat mixer scan band
"
4.0 K
2.0 to 40.0 K
"
Heat mix non-op band
"
1.0 K
0.5 to 3.0 K
"natural cooling" (at the heating circuit)
If all on-site components for the nat-
ural cooling function are installed (at
the heating circuit, see page 12), then
the system definition must be
extended to be able to use that func-
tion.
This setting can also be effected via
the system configuration (see
page 47).
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
Natural cooling
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Mixer active zone/dead zone
(cont.)
111
Heating circuit control settings
55
92
901
GB
Service
Summary of Contents for VITOCAL 300
Page 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Page 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Page 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Page 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Page 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Page 159: ...159 5592 901 GB...