6.FUNCTIONS
61
6-7. Gravitational Acceleration
This function corrects weight errors caused by the difference in local gravitational acceleration
when the calibration location and installation location of the scale are different.
No setting is required if the calibration location and installation location are in the same area.
Gravitational acceleration
CC-Link
0
47
01 to 16
MSB
LSB
RWw0006
RWw0005
RWw0004
Write the code No. and set value.
0
H
L
Code No.
Set value
remote register
Word size
Console
1) Select code 47.
2) Press the ENT key, and then set the
gravitational acceleration.
3) Determine the setting with the ENT key.
Gravitational
acceleration
01
9.806
02
9.805
03
9.804
04
9.803
05
9.802
06
9.801
07
9.800
08
9.799
09
9.798
10
9.797
11
9.796
12
9.795
13
9.794
14
9.793
15
9.792
16
9.791
Summary of Contents for F156