3.CC-LINK INTERFACE
15
3-4. Outline of the Buffer Memory for Communication
The Mitsubishi PLC CC-Link master/local unit communicates with the F156 by using the buffer
memory in the unit. Hereafter,
the master unit (master station) is called “M” and
the F156 (remote device station) is called “R” in the explanation.
Since one F156 occupies two stations, station numbers are set as shown below when two or
more F156s are connected. The upper column and lower column show the buffer name and
buffer address (head), respectively. As just described, the addresses allocated to the remote
stations in the master station change according to the station number.
Specified F156s are accessed by using these buffer addresses.
In the application program of the PLC, the buffer memory is accessed by the FROM/TO
instruction at A series.
The following explanations are given on the F156 of station No. 1.
Station
No.
Remote input
Remote output
Remote register
32 points/
station
32 points/
station
M
→
R
4 word/station
R
→
M
4 word/station
1
RX000h
RY000h
RW
w
0000
RWr0000
00E0h
0160h
01E0h
02E0h
RX020h
RY020h
RW
w
0004
RWr0004
00E2h
0162h
01E4h
02E4h
3
RX040h
RY040h
RW
w
0008
RWr0008
00E4h
0164h
01E8h
02E8h
RX060h
RY060h
RW
w
0012
RWr0012
00E6h
0166h
01ECh
02ECh
5
RX080h
RY080h
RW
w
0016
RWr0016
00E8h
0168h
01F0h
02F0h
1st
2nd
F156
F156
Summary of Contents for F156
Page 1: ...F156 WEIGHING CONTROLLER 07 JUN 2012 REV 1 40 OPERATION MANUAL CC Link Ver 1 10...
Page 115: ...7 REMOTE CONSOLE UNIT 106 Monitor change Change the display with the key...
Page 120: ...7 REMOTE CONSOLE UNIT 111 Monitor change Change the display with the keys 0 to 9 1 2 3 4 5 0...
Page 155: ...13 DIMENSIONS 146 13 DIMENSIONS...