Installation situations
Supporting con-
struction
Installation location
Minimum
thickness
[mm]
Class of per-
formance EI TT
(v
e
–h
o
, i ↔ o) S
up to
Installation
type
Installa-
tion
informa-
tion
in, fire protection block bulk-
head
100 – 200
EI 90 S
T
Solid ceiling slabs
in
100 (150)
2
EI 120 S
N
in, with concrete base
100
EI 90 S
N
in, with concrete base, multiple
mounting
100
EI 90 S
N
in, with concrete base, com-
bined assembly
100
EI 90 S
N
in, hollow stone ceilings
150
EI 90 S
N
in, hollow chamber ceilings
150
EI 90 S
N
in, ribbed ceilings
150
2
EI 90 S
N
in, composite ceilings
150
EI 90 S
N
in, combined with wooden
beam ceilings
150
EI 90 S
N
in, combined solid wood ceiling
150
EI 90 S
N
in, combined lightweight ceiling
3
150
EI 120 S
N
in, installation block ER
100 (150)
2
EI 90 S
E
underneath (horizontal duct),
installation kit WE / WE2
125
EI 120 S
E
above (horizontal duct), instal-
lation kit WE / WE2
125
EI 120 S
E
in, fire batt
100 (150)
2
EI 120 S
W
1
100 (150)
2
EI 90 S
W
1
Solid wood ceil-
ings
in
140
EI 90 S
N
112.5
EI 90 S
N
in, installation kit TQ / TQ2
140
EI 90 S
E
112.5
EI 90 S
E
Wooden beam ceil-
ings
in
167.5
EI 90 S
N
155
EI 60 S
N
142.5
EI 30 S
N
in, installation kit TQ / TQ2
167.5
EI 90 S
E
155
EI 60 S
E
1)
The class of performance depends on the installation details
2)
Thickness increased near the installation opening
3)
Cadolto system
4)
Depending on local conditions
N = Mortar-based installation
E = Installation kit
W = Fire batt
E = Dry mortarless installation
Installation
Installation situations
Fire damper Type FKRS-EU