5.11.9
Mortar-based installation in conjunction with lightweight ceilings
Fig. 120: Mortar-based installation into solid ceiling slab in conjunction with lightweight ceiling (Cadolto system),
shown upright (also applicable for suspended arrangement)
1
FKRS-EU
2.1
Mortar
2.2
Reinforced concrete
4.3
Modular ceiling (Cadolto system), installation
according to manufacturer's instructions and gen-
eral appraisal certificate
4.4
Partial concrete ceiling with reinforcement
7.5
Steel support structure
7.17
Trimmers, steel support structure
7.19
Fire-resistant cladding
9.2
Extension piece or duct
Up to EI 120 S
Additional requirements: mortar-based installation into solid ceiling slabs in conjunction with lightweight
ceilings
Modular ceiling (Cadolto)
≥
40 mm distance from fire damper to load-bearing structural elements
≥
45 mm distance between two fire dampers
Structural and fire resistance properties of the ceiling construction, including the attachment to the concrete or
any required reinforcement, have to be evaluated and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation in conjunction with ...
Fire damper Type FKRS-EU
139