Fig. 79: Dry mortarless installation into a lightweight partition wall with half-timbered construction, with installation kit
TQ / TQ2
1
FKRS-EU
2.11
Installation kit TQ / TQ2 with cover plate (two-
part with TQ2)
3.5
Half-timbered construction, cladding on both
sides
4.1
Solid ceiling slab / solid floor
6.8
Infill (cavities completely filled with mineral wool
≥
1000 °C,
≥
50 kg/m³, or bricks, aerated con-
crete, lightweight concrete, reinforced concrete
or clay)
6.13
Mineral wool strips A1, alternatively gypsum
mortar
7.9
Half-timbered construction
7.11
Trim panels, fire-resistant, double layer, stag-
gered joints
7.13
Cladding
7.14
Reinforcing board of the same material as the
wall
*
Installation near the floor analogous to
**
Cover plate shortened by others
Up to EI 120 S
EI 30 S
EI 30 to EI 90 S
Additional requirements: dry mortarless installation with installation kit TQ / TQ2 into lightweight partition
walls with timber support structure / half-timbered construction
Timber support structure or half-timbered construction, see
Installation kit TQ / TQ2, see
≥
200 mm distance between two fire dampers in separate installation openings
Installation
Lightweight partition walls with timber support ... > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
96
Summary of Contents for FKRS-EU
Page 176: ...Fire damper Type FKRS EU 176...