5.14.3
Fire damper remote from walls and ceilings
Fig. 139: FKRS-EU in a cladded duct
1
FKRS-EU
3.1
Solid wall
3.2
Lightweight partition wall with metal support struc-
ture, cladding on both sides
4.1
Solid ceiling slab
9.4
Sheet steel duct with L90 cladding and suspen-
sion system according to Promat® manual, con-
struction 478, latest edition
9.5
Suspension system (by others) consisting of:
a
Threaded rod M10
b
Hilti
®
mounting rail MQ 41
×
3 mm or equivalent
c
Hilti
®
drilled plate, MQZ L13 or equivalent
d
Hexagon nut M10 with washer
*
Additional ducting can be used
**
Suspension is required in connection with 9.4*