Fig. 40: Dry mortarless installation remote from a solid wall with wall connection, cladding on two sides
1
FKRS-EU
2.1
Mortar
2.6
Installation kit WE / WE2
3.1
Solid wall
4.1
Solid ceiling slab
5.7
Anchor bolt Hilti
®
HUS-6 or equivalent
6.13
Mineral wool,
≥
1000 °C,
≥
80 kg/m³, or gypsum
mortar to even out an uneven wall or ceiling
9.4
Sheet steel duct with fire-rated cladding and sus-
pension system according to Promat® manual,
construction 478, latest edition
9.5
Suspension system (by others) consisting of:
a
Threaded rod M10
b
Hilti
®
mounting rail MQ 41
×
3 mm or equivalent
c
Hilti
®
drilled plate, MQZ L13 or equivalent
d
Hexagon nut M10 with washer
Up to EI 120 S
Additional requirements: installation with installation kit WE / WE2 remote from solid walls with
wall attachment
Solid wall
Installation kit WE / WE2, see
Sheet steel ducts without any openings, with fire-resistant cladding (fittings with cladding according to instruc-
tions from Promat®)
≥
130 mm distance from the fire damper to the wall or ceiling slab
≥
260 mm distance between two fire dampers
Note:
For more installation details and for components to be provided by others, see the WE / WE2 installation
manual.
Installation
Solid walls > Installation with installation kit WE / WE2 re...
Fire damper Type FKRS-EU
52