background image

5 3/4" (146)

16" (406) STANDARD

NOM. DIA.

- 1/8" (3)

ACTUATOR

DRIVE 
SHAFT

INSTALLATION

RETAINING PLATES

INCLUDED

Model 1290F fire damper is ideal for applications where building
codes require a fire damper for the protection of ductwork
penetrations in walls or floors that have a fire resistance rating of
up to 2 hours. The 1290F is classified for use in dynamic "fans
on" systems where the HVAC system remains operative in the
event of a fire. Damper closure under airflow is assured.

The 1290F is an economical true round fire damper designed
and qualified specifically for point-of-origin fire containment
where round ductwork passes through metal or wood stud
drywall partitions and masonry walls or floors.

Features include the industry proven over-center knee lock
design with high torque spring/fusible link closure. The 1290F is
supplied as standard with a crank arm and locking screw which
holds the damper in the fully open position, but may also be used
for system balancing if required.

STANDARD CONSTRUCTION:

Frame:

20 ga. (1.0) galvanized steel integral sleeve and 
retaining plates.

Blade:

2 x 20 ga. (1.0) galv. steel laminated together. 
14 ga. (2.0) equivalent thickness.

Linkage:

Jackshaft to blade.

Bearings:

1/ 2" (13) dia. self-lubricating oilite bronze.

Axles:

1/ 2" (13) dia. plated steel double bolted to blades.

Jackshaft:

1/2" (13) dia. cadmium plated steel. Supplied with 
factory mounted hand locking quadrant.

Fusible Link:

165°F (74°C) standard. 212°F (100°C) available.

Sizes (Duct Dia.):

Note:

Dampers available in 1" (25) increments. Vertical or horizontal

installation.

OPTIONS:

BS

Stainless steel bearings

MLS-300

Position indicator switch pack
(8" (203) dia. minimum size required).

QUALIFICATIONS:

• UL 555 & CAN/ULC-S112 CLASSIFIED DYNAMIC FIRE 

DAMPER  1 1/2 hr. Label (File # R9492).

• Meets NFPA 80, 90A and 101 as well as IBC and NBC 

(Canada) Building Code requirements.

• California State Fire Marshal: Fire Damper Listing No. 

3225-0935:0101.

• Maximum velocity: 2000 fpm @ 4" w.g. (10 m/s @ 1 kPa).

Minimum

Maximum

6" (152) dia.

24" (610) dia.

Wall Thickness

Min. Sleeve Length

4 to 8 (102 to 203)

16 (406)

10 to 12 (254 to 305)

20 (508)

14 to 16 (356 to 406)

24 (610)

SCHEDULE TYPE:

PROJECT:

ENGINEER:

CONTRACTOR:

DATE

B SERIES

SUPERSEDES DRAWING NO.

4 - 28 - 14

1200

11 - 28 - 11

1290F-1

DYNAMIC ROUND FIRE DAMPER 

1 1/2 HR. LABEL • VERT. OR HORIZ.
FOR USE IN DYNAMIC OR STATIC SYSTEMS

MODEL: 1290F

Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.

For installation instructions, see IOM-1290FINST.

Dimensions are in inches (mm).

CCW

TO

OPEN

(Retaining Plates not shown)

Summary of Contents for 1290F

Page 1: ...inkage Jackshaft to blade Bearings 1 2 13 dia self lubricating oilite bronze Axles 1 2 13 dia plated steel double bolted to blades Jackshaft 1 2 13 dia cadmium plated steel Supplied with factory mounted hand locking quadrant Fusible Link 165 F 74 C standard 212 F 100 C available Sizes Duct Dia Note Dampers available in 1 25 increments Vertical or horizontal installation OPTIONS BS Stainless steel ...

Page 2: ...eel jackshaft to blade Bearings 1 2 13 dia stainless steel Axles 1 2 13 dia stainless steel double bolted to blades Jackshaft 1 2 13 dia stainless steel Supplied with factory mounted hand locking quadrant Fusible Link 165 F 74 C standard 212 F 100 C available Sizes Duct Dia Note Dampers available in 1 25 increments Vertical or horizontal installation CONSTRUCTION TYPE 304 Type 304 Stainless Steel ...

Page 3: ...0 Vdc Standard Mounting MS1 is damper open signal MS2 is damper closed signal Non Standard Mounting Important Installer must double check continuity of MS1 and MS2 before wiring to determine which switch signals the damper s open or closed position EXTERNAL RIGHT HAND MOUNTING FRONT VIEW LESS COVER COVER A A 2 7 8 73 3 76 4 1 8 105 MS 2 MS 1 BLUE YELLOW SECTION A A JACKSHAFT DRIVESHAFT EXTENSION C...

Page 4: ...0 94 100 47 400 189 01 3 2 50 02 5 03 8 1 25 15 37 04 10 08 20 05 13 06 15 7 174 6 5 150 125 4 100 3 75 25 62 PRESSURE DROP Pressure Drop tested per AMCA Standard 500 D Fig 5 5 PERFORMANCE DATA MODEL SERIES 1290F 1 1 2 HOUR LABEL AND 1290F SS 1 1 2 HOUR LABEL 1290F Maximum Performance Ratings UL 555 Fire Rating 1 1 2 Hour Maximum Velocity 2000 fpm 10 m s Maximum Pressure 4 in w g 1 kPa 1290F SS Ma...

Page 5: ...steel 1290F or stainless steel 1290F SS 4 Splice clips 20 gauge 1 0 galvanized steel 1290F or stainless steel 1290F SS two pairs for each plate 5 Steel or wood runner 6 Retaining clip 1 x 1 x 1 25 x 25 x 25 20 gauge 1 0 galvanized steel 1290F or stainless steel 1290F SS angle see note 5 7 10 sheet metal screw 8 1 8 3 dia steel pop rivet or 10 x 1 2 13 sheet metal screws or tack or spot welds 9 1 4...

Page 6: ...ngage metal or wood studs or runners On masonry installations the damper plate shown in Fig 3 should be used This has four equally spaced clips 1 x 1 x 1 25 x 25 x 25 20 gauge 1 0 which are attached to the plate and damper sleeve using 3 16 5 rivets tack or spotwelds Make sure that fasteners do not interfere with the operation of the damper blade For dampers 12 305 dia or less single side retainin...

Page 7: ...at source in a manner so no heat is directed towards the spring as the excessive heat can negatively affect the spring performance AS SOON AS THE LINK HAS MELTED THE SPRING WILL FORCE THE BLADES TO CLOSE INSTANTANEOUSLY THE BLADE PATH MUST BE KEPT CLEAR Reloading the spring assembly 2 Loosen the jackshaft from the bolt on crank arm quadrant located on the jackshaft side opposite of the spring asse...

Page 8: ...ove any obstructions dirt rust corrosion or other observed conditions that could impede proper damper operation Clean damper blades and other moving parts if necessary Use of a mild detergent or solvents is recommended for any cleaning required 2 Check closure springs If damaged or defective repair or replace 3 Linkage and jackshaft bearing brackets should be lubricated with a dry lubricant such a...

Page 9: ...ire smoke and smoke dampers Position Indicator Microswitch Data Switch Type Single Pole double throw 2 15 Amps 1 3 HP 125 250 Vac or 24 Vdc 1 2 Amp 125 Vdc 1 4 Amp 250 Vdc EXTERNAL RIGHT HAND MOUNTING FRONT VIEW LESS COVER COVER A A 2 7 8 73 3 76 4 1 8 105 MS 2 MS 1 BLUE YELLOW SECTION A A JACKSHAFT DRIVESHAFT EXTENSION CONDUIT CONNECTION DUCT OR SLEEVE 13 16 21 JACKSHAFT MOUNTING BRACKET 1 6 7 5 ...

Page 10: ... actuator MS1 is damper open signal MS2 is damper closed signal Important Installer must double check continuity of MS1 and MS2 before wiring to confirm which switch signals the damper s open or closed position 2 Connect external wiring and electrical power supply 120 or 24 Vac in accordance with N E C and any applicable local codes 3 Replace junction box cover and check operation L2 L1 CLOSED RED...

Reviews:

Related manuals for 1290F