Fig. 134: Mortar-based installation into historical wooden beam ceilings, shown upright (also applicable for sus-
pended arrangement)
1
FKRS-EU
2.1
Mortar
2.2
Concrete
6.26
Plaster*
6.28
Ceiling fill*
7.10
Trim panels
7.15
Wooden floorboard / floor covering*
7.16
Wooden beam
7.26
Hollow stone*
9.2
Extension piece or duct
*
Illustration representative, other ceiling construc-
tions possible according to local conditions and
ceiling manufacturers
EI 30 S
Additional requirements: mortar-based installation into historical wooden beam ceilings
Historical wooden beam ceiling, see
≥
75 mm distance from fire damper to load-bearing structural elements
≥
200 mm distance between two fire dampers in separate installation openings
Structural and fire resistance properties of the ceiling construction, including the attachment to the mortar/
concrete or any required reinforcement, have to be evaluated and ensured by others.
Installation
Wooden beam ceilings > Mortar-based installation into historical wood...
Fire damper Type FKRS-EU
153