5.12.2
Dry mortarless installation with installation kit TQ / TQ2 into solid wood ceilings
Fig. 127: Dry mortarless installation with installation kit TQ / TQ2 into solid wood ceiling, upright and suspended
1
FKRS-EU
2.11
Installation kit TQ / TQ2 with cover plate (two-
part with TQ2)
4.5
Solid wood ceiling
5.3
Wood screw min. 5
×
70 mm
7.19
Fire-resistant cladding
–
Up to EI 90 S
Additional requirements: dry mortarless installation with installation kit TQ / TQ2 into solid wood ceilings
Installation kit TQ / TQ2, see
≥
75 mm distance from the fire damper to load-bearing structural elements (structure 100 mm)
≥
200 mm distance between two fire dampers in separate installation openings
Structural and fire resistance properties of the ceiling construction, including the attachment to the concrete or
any required reinforcement, have to be evaluated and ensured by others.
Installation
Solid wood ceilings > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
147