10.2 Replacing the fusible link
Fig. 153: Removing the fusible link holder
1.6
Handle
10.15 Fusible link holder
10.17 Screw
1.
Close the damper blade.
2.
Release screws (10.17) on the fusible link holder
(10.15).
3.
Remove fusible link holder (10.15) from the fire
damper. While doing so, slightly press down the
tab (1.6) of the handle.
Fig. 154: Replacing the fusible link
10.15 Fusible link holder
10.18 Fusible link
10.20 Spring
1.
Cover fusible link holder (10.15) as shown and
press together in the direction of the arrow to ten-
sion the spring (10.20).
2.
Remove old fusible link (10.18), hook in new
fusible link (10.18).
Fig. 155: Install the fusible link holder
1.6
Handle
10.15 Fusible link holder
10.17 Screw
1.
Press the tab of the handle (1.6) slightly against
the handle and push the fusible link holder (10.15)
into the fire damper and
2.
fasten with screws (10.17).
ð
Carry out functional test.
Maintenance
Replacing the fusible link
Fire damper Type FKRS-EU
166
Summary of Contents for FKRS-EU
Page 176: ...Fire damper Type FKRS EU 176...