5.13.2
Dry mortarless installation with installation kit TQ / TQ2 into wooden beam ceil-
ings
Fig. 130: Dry mortarless installation with installation kit TQ / TQ2 into wooden beam / laminated beam ceiling, upright
(illustration representative, alternative ceiling construction possible on request)
1
FKRS-EU
2.11
Installation kit TQ / TQ2 with cover plate (two-
part with TQ2)
5.3
Wood screw min. 5
×
70 mm
6.25
Mineral wool fill if required
7.11
Trim panel, same construction as 7.19
7.15
Wood sheet, at least 600 kg/³
7.16
Wooden beam / gluelam min. 100
×
80 mm
(reduce distances between wooden beams to the
size of the installation opening)
7.17
Trimmers, wooden beam / gluelam
min. 100
×
80 mm
7.19
Fire-resistant cladding (ceiling-dependent)
Up to EI 90 S
Up to EI 60 S
EI 30 S
Installation
Wooden beam ceilings > Dry mortarless installation with installation ...
Fire damper Type FKRS-EU
150