5.12 Solid wood ceilings
5.12.1
Mortar-based installation into solid wood ceilings
Fig. 126: Mortar-based installation into a solid wood ceiling, suspended or upright
1
FKRS-EU
2.1
Mortar
4.5
Solid wood ceiling
7.19
Fire-resistant cladding
9.2
Extension piece or duct
–
Up to EI 90 S
Additional requirements: mortar-based installation into solid wood ceilings
≥
75 mm distance from fire damper to load-bearing structural elements
≥
200 mm distance between two fire dampers in separate installation openings
Structural and fire resistance properties of the ceiling construction, including the attachment to the concrete or
any required reinforcement, have to be evaluated and ensured by others.
Installation
Solid wood ceilings > Mortar-based installation into solid wood ceil...
Fire damper Type FKRS-EU
146