5.11.7
Mortar-based installation in conjunction with wooden beam ceilings
Fig. 118: Mortar-based installation into solid ceiling slab in conjunction with wooden beam / laminated beam ceilings,
shown upright (also applicable for suspended arrangement)
1
FKRS-EU
2.1
Mortar
2.2
Reinforced concrete
7.11
Trim panel, same construction as 7.19
7.15
Wooden floorboard / floor tiles (different ceiling
construction may be possible)
7.16
Wooden beam / gluelam (reduce distances
between wooden beams to the size of the instal-
lation opening)
7.17
Trimmers, wooden beam / gluelam
7.18
Formwork
7.19
Fire-resistant cladding (ceiling-dependent)
9.2
Extension piece or duct
Up to EI 90 S
Additional requirements: mortar-based installation into solid ceiling slabs in conjunction with wooden
beam / laminated beam ceilings
Wooden beam ceiling, see
≥
40 mm distance from fire damper to load-bearing structural elements
≥
45 mm distance between two fire dampers
Structural and fire resistance properties of the ceiling construction, including the attachment to the concrete or
any required reinforcement, have to be evaluated and ensured by others.
Installation
Solid ceiling slabs > Mortar-based installation in conjunction with ...
Fire damper Type FKRS-EU
137