E6581697
D-11
4
60 Hz default setting (
=
)
Setting
to
sets the following parameters for base frequency 60 Hz use.
(The setting values of other parameters are not changed.)
Max. frequency (
)
:
60Hz
Upper limit frequency (
)
:
60Hz
Base frequency 1 (
)
:
60Hz
Base frequency 2 (
)
:
60Hz
VIA input point 2 frequency (
)
:
60Hz
VIB input point 2 frequency (
)
:
60Hz
VIC input point 2 frequency (
)
:
60Hz
Automatic light-load high-speed operation
Process upper limit (
)
:
60Hz frequency
(
)
:
60Hz
Motor rated RPM (
)
:
1710 min
-1
Communication command point 2 frequency
(
)
:
60Hz
Default setting 1 (
=
)
Setting
to
will return parameters to the standard values that were programmed at the factory.
,
When
is set,
is displayed for a short time after the settings are configured, and then
disappears. Then the inverter is in standard motor mode. In this case, the trip history data is cleared.
Trip record clear (
=
)
Setting
to
initializes the past eight sets of recorded error history data.
,
The parameter does not change.
Cumulative operation time clear (
=
)
Setting
to
resets the cumulative operation time to the initial value (zero).
Initialization of type information (
=
)
Setting
typ
to
clears the trips when an
format error occurs. But if the
displayed, call us.
Be aware that the following parameters do not return to the default settings even if
=
is set for
maintainability. (To initialize all parameters, set
=
)
・
:
Overload characteristic selection
・
~
:
VIA/VIB/VIC input bias / gain
・
:
Meter selection
・
:
Logic output/pulse train output selection
・
:
Meter adjustment gain
・
:
Analog output signal selection
・
:
Checking the region setting
・
:
Inclination characteristic of analog output
・
:
Analog input terminal selection
・
:
Analog output bias
・
:
Analog/logic input selection
・
:
Free notes