E6581697
F-82
6
■
Flow of operation when
f602
=
Occurrence of a
trip
Reset the
inverter by
panel or
terminal
operation.
Turn power off,
then turn it back
on to reset the
inverter.
Completion of reset
If the cause of the
trip is not
eliminated
If the cause of the
trip is eliminated
Normal operation
The relay trips again.
・
Display of the cause
・
Failure signal FL
activated
Trip state is retained
・
Display of the cause
・
Failure signal FL not
activated
6.24.4 Emergency
stop
f515
: Deceleration time at emergency stop
f603
: Emergency stop selection
f604
: DC braking time during emergency stop
Function
Set the stop method for an emergency. When operation stops, a trip occurs (
e
displays) and failure
signal FL operates.
When
f603
is set to
2
(Emergency DC braking), set
f251
(DC braking amount) and
f604
(DC braking time during emergency stop).
When
f603
is set to
3
(Deceleration stop), set
f515
(Deceleration time at emergency stop).
1) Emergency stop from terminal
Emergency stop occurs at contact a or b. Follow the procedure below to assign a function to an input
terminal and select a stop method.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f515
Deceleration time at emergency stop
0.0-3600 (360.0) (s)
10.0
f603
Emergency stop selection
0: Coast stop
1: Deceleration stop
2: Emergency DC braking
3: Deceleration stop (
f515
)
4: Quick deceleration stop
5: Dynamic quick deceleration stop
0
f604
DC braking time during emergency
stop
0.0-25.5 (s)
1.0
f251
DC braking current
0 - 100 (%)
50