6.6.5 Setting of frequency with the pulse train input
146
: Logic input / pulse train input selection (S2)
378
: Number of pulse train input
679
: Pulse train input filter
Function
These parameters are used to set an output frequency by means of pulse train input signal of S2
terminal.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f146
Logic input / pulse train input selection
(S2)
0: Logic input
1: Pulse train input
0
f378
Number of pulse train input
100-5000 (pps)
250
f679
Pulse train input filter
2-1000 (ms)
2
,
This function is valid when the parameter
fmod
=
11
(Pulse train input) and
f146
=
1
(Pulse train
input) are set.
,
Number of pulses per 1Hz is set by parameter
f378
.
,
Example of setting
f378
= 250 (pps) : Input signal = 250 (pps)
Output frequency = 1.0 (Hz)
Input signal = 1k (pps)
Output frequency = 4.0 (Hz)
Input signal = 20k (pps)
Output frequency = 80.0 (Hz)
f378
= 500 (pps) : Input signal = 500 (pps)
Output frequency = 1.0 (Hz)
Input signal = 1k (pps)
Output frequency = 2.0 (Hz)
Input signal = 20k (pps)
Output frequency = 40.0 (Hz)
Note) Minimum number of pulses to inputting S2 terminal is 10 pps, and Maximum is 20 kpps.