6.29.8 Canceling the operation command
f719
: Canceling of operation command
Function
This parameter allows you to select operation command retained or operation command canceled,
when coast stop occurs due to standby terminal function (ST), coast stop command terminal function
or open between control terminal STO and +SU, and when under voltage in main circuit alarm occurs,
during panel operation or RS485 communication operation.
Parameter setting
At coast stop
Under voltage in main circuit alarm occurrence
=
Operation command canceled
Operation command retained
=
Operation command retained
=
Operation command canceled
Operation command retained :
Inverter restarts due to canceling coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm (
)
occurs.
Operation command canceled :
Inverter doesn’t restart after coast stop or occurring the under voltage in main circuit alarm (
).
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title
Function
Adjustment range
Default setting
f719
Canceling of operation
command
0: Panel operation command canceled
(cleared)
1: Operation command retained
2: Panel/Communication operation
command canceled (cleared)
1
[Setup example of input terminal for standby terminal function and coast stop command function]
When it is assigned to the RES terminal.
Title
Function
Adjustment range
Setting
f113
Input terminal selection 3A
(RES)
0-203
6: ST (Standby)
f113
Input terminal selection 3A
(RES)
0-203
96: FRR (Coast stop command)
Setting value 7, 97 are reverse signal.