The inverter was factory-configured by default so that if both forward and reverse run signals from
terminal board are ON simultaneously, the motor will decelerate to stop.
However, you can use the parameter
to select deceleration stop or reverse run.
5.9 Maximum
frequency
: Maximum frequency
Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
Output frequency
(Hz)
When
=80Hz
When
=60Hz
80Hz
60Hz
0 100% Frequency setting signal (%)
・
This function determines the value
in line with the ratings of the motor
and load.
・
Maximum frequency cannot be
adjusted during operation.To
adjust, first stop
the inverter.
+
If
is increased, adjust the upper limit frequency
as necessary.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Maximum frequency
30.0-500.0 (Hz)
80.0