E6581697
G-9
7
(3) The logical product (AND) or logical sum (OR) of the two
functions assigned is put out as a signal.
■
Setting of output terminal function
Terminal
symbol
Title
Function
Adjustment range
Default setting
RY-RC
Output terminal selection 1A
4
(LOW)
OUT
Output terminal selection 2A
6
(RCH)
RY-RC
Output terminal selection 1B
255
(always ON)
OUT
Output terminal selection 2B
0-255
255
(always ON)
0:
and
and
1:
or
and
2:
and
or
RY-RC/
OUT
Output terminal logic selection
3:
or
or
0
Two different functions can be assigned to the output terminals (RY-RC and OUT-NO), and two logics with
different functions can be selected using
.
The logical product (AND) or logical sum (OR) of the two functions assigned is put out as a signal, depending
on the setting of parameter
.
If
=
, the logical sum (AND) of
and
will be output to RY-RC.
The logical product (OR) of
and
will be output to OUT-NO.
If
=
, the logical product (OR) of
and
will be output to RY-RC.
The logical sum (AND) of
and
will be output to OUT-NO.
If
=
, the logical sum (AND) of
and
will be output to RY-RC.
The logical product (OR) of
and
will be output to OUT-NO.
If
=
, the logical product (OR) of
and
will be output to RY-RC.
The logical product (OR) of
and
will be output to OUT-NO.
,
To assign only one function to output terminals, assign the function to
and
while leaving
f137
to
f139
as they are set by default.
Note:
f138
(OUT-NO): Enable only when
f669
=
0
Disabled and the set value cannot be read out, if
f669
is set to 1.