E6581697
K-22
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0730
Panel frequency
setting prohibition
(
)
- -
0:
Permitted
1: Prohibited
0
6.29.1
0731
Disconnection
detection of
extension panel
- -
0:
Permitted
1: Prohibited
0
0732
Local/remote key
prohibition of
extension panel
- -
0:
Permitted
1: Prohibited
1
6.13
6.29.1
0733
Panel operation
prohibition
(RUN key)
- -
0:
Permitted
1: Prohibited
0
0734
Panel emergency
stop operation
prohibition
- -
0:
Permitted
1: Prohibited
0
0735
Panel reset
operation
prohibition
- -
0:
Permitted
1: Prohibited
0
0736
/
change prohibition
during operation
- -
0:
Permitted
1: Prohibited
1
6.29.1
0737
All key operation
prohibition
- -
0:
Permitted
1: Prohibited
0
0738
Password setting
(
)
-
-
0: Password unset
1-9998
9999: Password set
0
0739
Password
verification
-
-
0: Password unset
1-9998
9999: Password set
0
0740
Trace selection
-
-
0: Disabled
1: At tripping
2: At triggering
3: 1+2
1
6.30
0741
Trace cycle
-
-
0: 4ms
1: 20ms
2: 100ms
3: 1s
4: 10s
2
0742
Trace data 1
-
-
0
0743
Trace data 2
-
-
1
0744
Trace data 3
-
-
2
0745
Trace data 4
-
-
0-42
3
0746 Status
monitor
filter
ms 1/1
8-1000
200 6.29.7
0748 Integrating
wattmeter
retention selection
- -
0:
Disabled
1: Enabled
0
6.31
0749 Integrating
wattmeter display
unit selection
- -
0:1=1kWh
1:1=10kWh
2:1=100kWh
3:1=1000kWh
*2
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
Summary of Contents for TOSVERT VF-MB1
Page 350: ...2011 07 ...