1) 0-10Vdc voltage input adjustment (VIA, VIB terminals)
Point settings adjust the
frequency command for the
voltage input.
Gradient and bias can be set
easily.
/
100 (%)
10V voltage signal
/
0 ( Hz)
/
0 (%)
0
/
50/60 (Hz)
Frequency commnd
2) 4-20mAdc current input adjustment (VIC terminal)
Point settings adjust the frequency
command for the current input.
Ramp and bias can be easily set.
With a current input of 0 to 20 mA,
set
to
.
100 (%)
20mA current signal
0 ( Hz)
20 (%)
4mA
50/60 (Hz)
Frequency commnd
3) -10-+10 Vdc voltage input adjustment (VIB terminal)
Point settings adjust the
frequency command for
the voltage input.
Ramp and bias can be
easily set.
f213
Forward run
Reverse run