E6581697
K-32
11
Table of input terminal functions 2
Function
No.
Code Function
Action
Reference
50
HD
Operation hold (hold of 3-wire operation)
ON: F (forward run), R: (reverse run) held, 3-wire operation
OFF: Deceleration stop
7.2.1
51 HDN Inversion
of
operation hold (hold of 3-wire
operation)
Inversion of HD
52
IDC
PID integral/differential clear
ON: Integral/differential clear, OFF: Clear canceled
6.20
53
IDCN
Inversion of PID integral/differential clear
Inversion of IDC
54
PIDSW
PID characteristics switching
ON: Inverted characteristics of
selection
OFF: Characteristics of
selection
55
PIDSWN
Inversion of PID characteristics switching
Inversion of PIDSW
56
FORCE
Forced run operation
ON: Forced run operation if specified faults are occurred
(
frequency)
OFF: Normal operation
6.25
57
FORCEN
Inversion of forced run operation
Inversion of FORCE
58
FIRE
Fire speed operation
ON: Fire speed operation (
frequency)
OFF: Normal operation
59
FIREN
Inversion of fire speed operation
Inversion of FIRE
60
DWELL
Acceleration/deceleration suspend signal
ON: Acceleration/deceleration suspend
OFF: Normal operation
6.19
61
DWELLN
Inversion of acceleration/deceleration
suspend signal
Inversion of DWELL
62
KEB
Power failure synchronized signal
ON: Deceleration stop with synchronizing when power failure
OFF: Normal operation
6.15.2
63
KEBN
Inversion of power failure synchronized
signal
Inversion of KEB
64
MYF
Logic sequence function trigger signal
ON: Trigger(start operation) signal
of logic sequence function
OFF: Normal operation
6.36
65
MYFN
Inversion of logic sequence function trigger
signal
Inversion of MYF
70, 71
Factory specific coefficient
-
*1
74
CKWH
Integrating wattmeter(kwh) display clear
ON: Integrating wattmeter(kwh) monitor display clear
OFF: Disabled
6.31
75
CKWHN
Inversion of integrating wattmeter display
clear
Inversion of CKWH
76
TRACE
Trace back trigger signal
ON: Trigger(start) signal
of trace function
OFF: Disabled
6.30
77
TRACEN
Inversion of trace back trigger signal
Inversion of TRACE
78
HSLL
Light-load high-speed operation prohibitive
signal
ON: Light-load high-speed operation
prohibited
OFF: Light-load high-speed operation
permitted
6.17
79
HSLLN
Inversion of light-load high-speed operation
prohibitive signal
Inversion of HSLL
80
HDRY
Holding of RY-RC terminal output
ON: Once turned on, RY-RC are held on.
OFF: The status of RY-RC changes in real time according to
conditions.
7.2.2
81
HDRYN
Inversion of holding of RY-RC terminal
output
Inversion of HDRY
82
HDOUT
Holding of OUT-NO terminal output
ON: Once turned on, OUT-NO are held on.
OFF: The status of OUT-NO changes in real time according
to conditions.
83 HDOUT
N
Inversion of holding of OUT-NO terminal
output
Inversion of HDOUT
88
UP
Frequency UP
ON: Frequency increased
OFF: Frequency increase canceled
6.6.3
89
UPN
Inversion of frequency UP
Inversion of UP
90
DWN
Frequency DOWN
ON: Frequency decreased
OFF: Frequency decrease canceled
91
DWNN
Inversion of frequency DOWN
Inversion of DWN
92 CLR Clear
frequency
UP/DOWN
OFF
¤
ON: Clear frequency UP/DOWN
93
CLRN
Inversion of clear frequency UP/DOWN
Inversion of CLR
*1: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.