E6581697
F-6
6
6.2.2
Changing the voltage range of VIB terminal
f107
: Analog input terminal selection (VIB)
Function
This parameter allows you to choose the voltage signal input for the VIB terminal.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f107
Analog input terminal
selection (VIB)
0: 0-+10V
1: -10-+10V
0
,
f107
=
0
: Input 0 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/1000 between 0 to +10Vdc.
,
f107
=
1
: Input -10 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/1000 between -10 to +10Vdc.
6.2.3
Changing the functions of VIA and VIB terminals
f109
: Analog/logic input selection (VIA/VIB)
Function
This parameter allows you to choose between analog signal input and contact signal input for the VIA
and VIB terminals.
[Parameter setting]
Title
Function
Adjustment range
Default setting
0: Analog input for communications
VIB
-
analog input
1: VIA - analog input
VIB
-
contact input (Sink)
2: VIA - analog input
VIB
-
contact input (Source)
3: VIA
-
contact input (Sink)
VIB
-
contact input (Sink)
f109
Analog/logic input
selection
(VIA/VIB)
4: VIA
-
contact input (Source)
VIB
-
contact input (Source)
0
Note) When using VIA and VIB terminals as contact input terminals, be sure to insert a resistor between P24
terminal and VIA/VIB terminals in sink logic connection, and insert a resistor between VIA/VIB terminals
and CC terminal in source logic connection. (Recommended resistance: 4.7k
-1/2W)