E6581697
F-97
6
2) Multiplicative override
In this mode, each output frequency is multiplied by an externally override frequency.
[Ex.1: VIA (Reference frequency), VIC (Override input)]
[Ex.2: VIB (Reference frequency), VIA (Override input)]
Ex.1:
f660
=
0
(Disabled),
f661
=
3
(VIC input),
fmod
=
1
(VIA input),
fh
=
8=0
,
ul
=
8=0
VIA input, (
f201
=
0
,
f202
=
=0
,
f203
=
100
,
f204
=
8=0
)
VIC input (
f216
=
0
,
f220
=
0
,
f218
=
100
,
f221
=
100
)
Setting of VIA input: Refer to Section 7.3.1, Setting of VIC input: Refer to Section 7.3.2.
Output frequency = Reference frequency × {1 + Override (VIC input [%]/100)}
Ex.2:
f660
=
0
(Disabled),
f661
=
1
(VIA input),
fmod
=
2
(VIB input),
fh
=
8=0
,
ul
=
8=0
VIB input (
f210
=
0
,
f211
=
=0
,
f212
=
100
,
f213
=
8=0
)
VIA input (
f201
=
0
,
f205
=
0
,
f203
=
100
,
f206
=
100
)
Setting of VIB input: Refer to Section 7.3.3, Setting of VIA input: Refer to Section 7.3.1.
Output frequency = Reference frequency × {1 + Override (VIA input [%]/100)}
Ex.3:
Title
Function
Adjustment range
Default setting
f729
Operation panel override multiplication gain
-100
- +
100
%
0
Output frequency = Reference frequency × {1 + Override (
f729
setting value [%]/100}
Output
frequency
0
10V
Over-ridden frequency
Output
frequency
0
10V
Over-ridden frequency
VIA input
(Reference
frequency)
(
)
VIB input
(Reference
frequency)
(
)
Reverse run
Forward run
-
10V