E6581697
F-84
6
[Parameter setting]
Title
Function
Adjustment range
Default setting
f605
Output phase failure detection
selection
0: Disabled
1: At start-up (only one time after
power on)
2: At start-up (each time)
3: During operation
4: At start-up + during operation
5: Detection of cutoff on output side
0
Note1) A check for output phase failures is made during auto-tuning, regardless of the setting of this parameter.
Note2) When parameter
pt
=
5
or
6
is selected,
f605
=
3
to
5
do not work.
6.24.6 Input phase failure detection
f608
: Input phase failure detection selection
Function
This parameter detects inverter input Phase failure. If the abnormal voltage status of main circuit
capacitor persists for few minutes or more, the tripping function and the FL relay will be activated.
Trip display is
eph1
. Detection may not be possible when operating with a light load, or when the
motor capacity is smaller than the inverter capacity.
If the power capacity is larger than the inverter capacity (more than 200kVA or more than 10 times),
detection errors may occur. If this actually happens, install an AC reactor .
f608
=
0
: No tripping. (Failure signal FL not activated)
f608
=
1
: Phase failure detection is enabled during operation. The inverter will trip if the abnormal voltage
status of main circuit capacitor persists for few minutes or more. (Failure signal FL activated)
[Parameter setting]
Title
Function
Adjustment range
Default setting
f608
Input phase failure detection selection
0: Disabled
1: Enabled
1
Note1: Setting
to
(input phase failure detection: disabled) may result in a breakage of the
capacitor in the inverter main circuit if operation is continued under a heavy load in spite of the
occurrence of an input phase failure.
Note2: Parameter
f608
is invalid for single-phase input model.
Note3: When operating the inverter with DC input, set
f608
=
0
(none).