Strata CTX670 Installation
Site Requirements
3-2
Strata CTX I&M 10/02
Site Requirements
Input Power
The CTX670 requires an input power source of 115±10VAC or 208±20VAC or 240±20VAC, 50/
60 Hz, single phase. For up to five cabinets; 208VAC or 240VAC is required for six or seven
cabinets. The system requires one or two AC outlets that must be dedicated to system use, fused,
and grounded.
Each Remote Expansion Cabinet requires 3.2 amps. maximum. The remote cabinet installation
requires one or two AC outlets that must be dedicated to system use, fused, and grounded.
See Cabinet Installation Considerations for complete AC power cabling, ground wiring and
battery installation instructions for local and remote cabinets.
CAUTION!
To avoid accidental power turn-off, do not use an On/Off wall switch for AC
circuits dedicated for the use of CTX670.
A reserve power source (two or four customer-supplied 12VDC batteries) can be connected to the
CTX670 to serve as a backup in case of power failure.
Separate reserve power may be required for remote expansion cabinets.
Clearance and Location
The Base and optional Expansion Cabinets can be either floor or wall mounted.
Figure 3-1
shows
the minimum clearance requirements for up to seven cabinets.
Notes
•
Floor mounting requires the following additional hardware:
•
BFIF – floor mounting stands and brackets.
•
BCCB – electrical conduit box, if three or more cabinets are installed.
•
Wall mounting requires a plywood (3/4 inch thick) backboard.
When selecting a location for the cabinets, the location must be:
•
Dry and clean
•
Well-ventilated
•
Well-illuminated
•
Easily accessible
The location must not be:
•
Subject to extreme heat or cold
•
Subject to corrosive fumes, dust, or other airborne contaminants
•
Subject to excessive vibration
•
Next to television, radio, office automation, or high frequency equipment
Optional customer-supplied reserve batteries require a well-ventilated location close (within nine
feet) to the CTX670 cabinets.
Summary of Contents for Strata CTX100
Page 16: ...Introduction Related Documents Media xii Strata CTX I M 10 02 ...
Page 94: ...Strata CTX100 Installation Installing the CTX100 Cabinet 2 24 Strata CTX I M 10 02 ...
Page 150: ...Strata CTX670 Installation Remote Expansion Cabinet Unit 3 56 Strata CTX I M 10 02 ...
Page 188: ...PCB Installation Network Requirements 4 38 Strata CTX I M 10 02 ...
Page 238: ...T1 Loop Back Testing 6 12 Strata CTX I M 10 02 ...
Page 310: ...Station Apparatus 2000 series Telephones 8 48 Strata CTX I M 10 02 ...
Page 342: ...Peripheral Installation Station Message Detail Recording SMDR 9 32 Strata CTX I M 10 02 ...