Time-Based Alternation Process Hold Mode Response Time
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, while running in the
Process Hold
mode, this parameter sets the time that the system may operate within the
maximum or minimum
Virtual Linear Pump
zones before turning the ASD on
or off, respectively.
Direct Access Number — F438
Parameter Type —
Numerical
Factory Default —
7.5
Changeable During Run —
No
Minimum — 0.0
Maximum — 6553.5
Units — Seconds
Time-Based Alternation Direct Mode Response Time
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, while running in the
Direct
mode,
this parameter sets the time that the system may operate within the maximum or
minimum
Virtual Linear Pump
zones before turning the ASD on or off,
respectively.
Direct Access Number — F439
Parameter Type —
Numerical
Factory Default —
1000
Changeable During Run —
No
Minimum — 0
Maximum — 65535
Units — Seconds
Power Running Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting.
If
Setting
is selected, the value set at
is used as the
Power Running
Torque Limit 1
input.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
(Setting)
Direct Access Number — F440
Parameter Type —
Selection List
Factory Default —
Changeable During Run —
Yes
Power Running Torque Limit 1 Level
Program
Torque
Torque Limit Settings
This parameter provides a value for the
Power Running Torque Limit 1
setting if the
F441 setting
is selected at parameter
.
This value provides the positive torque upper-limit for the
1
motor.
Direct Access Number — F441
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the
Regenerative Torque Limit
control signal.
If
Setting
is selected, the value set at
is used for this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
(Setting)
Direct Access Number — F442
Parameter Type —
Selection List
Factory Default —
Setting
Changeable During Run —
Yes