P9 ASD Installation and Operation Manual
PTC2 Thermal Selection
Program
Special
Special Parameters
PTC2 Thermal Selection
This parameter
Enables/Disables
the optional external thermal detection circuit
of the
Expansion IO Card Option 2
. A thermistor is connected from
TH1+
to
TH1-
of
TB4
on the
Expansion IO Card Option 2
.
Should the thermistor resistance reading fall below 50
because of an over-
temperature condition or exceed 3000
because of an open circuit, an
External
Thermal Fault
(OH2) will be incurred.
Note:
While this parameter is
Enabled
, the system cannot be restarted
until the thermistor value recovers to the level of 1.8 k
from an
over-temperature condition. An
Auto-Restart
will not be
initiated subsequent to an
External Thermal
Trip
(OH2). A
manual restart will be required in the event of an
OH2
trip.
Settings:
0 — Disabled
1 — Detect Disconnect
Direct Access Number — F638
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Braking Resistance Overload Time (10x rated torque)
Program
Protection
Dynamic Braking
This parameter sets the time that the braking resistor is allowed to sustain an
overload condition before a trip is incurred.
This feature is useful for applications that have a fluctuating load or for loads
that require a long deceleration time.
Direct Access Number — F639
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
No
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Step-Out Current Detection Level
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.
Direct Access Number — F640
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 10
Maximum — 150
Units — %
Step-Out Current Detection Time
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.
Direct Access Number — F641
Parameter Type —
Numerical
Factory Default —
00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 25.0
Units — Seconds