120
P9 ASD Installation and Operation Manual
RX2 (AI1) Input Point 2 Rate
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Torque Control
mode.
Torque Control
is accomplished by establishing an associated
V/f
output
pattern for a given
RX2
(AI1) input level.
This parameter sets
RX2
(AI1)
Input Point 2 Rate
and is the output torque
value that is associated with the setting of
RX2
(AI1)
Input Point 2 Setting
when operating in the
Torque Control
mode.
This value is entered as -250% to +250% of the rated torque.
See
RX2
(AI1)
Input Point 1 Rate
) for additional information on this
parameter.
Direct Access Number — F227
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %