P9 ASD Installation and Operation Manual
151
(Virtual Linear Pump) Sleep Timer Delay
Virtual Linear Pump
Sleep Timer Setting
During a properly configured
Virtual Linear Pump
operation, and once
, this parameter establishes the time that system operation will
be allowed to operate within the
threshold
before the ASD output to the motor is terminated.
See
for additional information on this parameter.
Direct Access Number — F383
Parameter Type —
Numerical
Factory Default —
300
Changeable During Run —
Yes
Minimum — 1
Maximum — 63335
Units — Seconds
(Virtual Linear Pump) Direct Operation Command Value
Program
Virtual Linear Pump
Virtual Linear Pump Settings
During a properly configured
Virtual Linear Pump
operation while operating
in the
Direct
mode and using the EOI for system control, this parameter
establishes the
Virtual Linear Pump
level.
This parameter setting is effective
ONLY
while operating in the
Direct
mode
and while receiving a command from the EOI. The end value of this parameter
setting appears in the
Frequency Command
screen as shown below.
Direct Access Number — F384
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 10
Maximum — 165
(Virtual Linear Pump) Auto Start-Stop Mode
Virtual Linear Pump
Auto Start-Stop Mode Enable
During a properly configured
Virtual Linear Pump
operation, this parameter
Enables/Disables
the ability of the system to receive transducer input to
manage system starts and stops as it pertains to the process variable.
This parameter is also used to select the ASD response (Stop or Start) upon
meeting the criteria of
and
settings.
On Forward
= Run ASD while measured signal is
setting and stop
setting.
On Reverse
= Run ASD while measured signal is
setting and stop ASD
setting.
Settings:
0 — Off
1 — On Forward
2 — On Reverse
Direct Access Number — F385
Parameter Type —
Selection List
Factory Default —
Off
Changeable During Run —
Yes
WARNING
The Auto Start-Stop operating mode may result in the
unexpected Start or Stop of the motor. Signs to this effect are
to be posted at the location of the motor/pump.