152
P9 ASD Installation and Operation Manual
(Virtual Linear Pump) Auto Start-Stop Delay Timer
Virtual Linear Pump
Auto Start-Stop Delay Timer
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the time that the
Start-Stop
and
must be
maintained to activate the
Auto Start-Stop
function.
This feature is used to minimize system responses to rapid fluctuations in the
feedback signal.
See
for additional information on this parameter.
Direct Access Number — F387
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6553.5
Units — Seconds
(Virtual Linear Pump) Auto Start-Stop Lower Threshold
Virtual Linear Pump
Auto Start-Stop Threshold Setting
During a properly configured
Virtual Linear Pump
operation while in the
On
Forward
or
On Reverse
modes (
), this parameter establishes the lower
level of the
Auto Start-Stop
threshold.
See
for additional information on this parameter.
The unit of measure for this parameter may be one of the following types — the
type is selected while running the
Virtual Linear Pump Setup Wizard
.
• PSI
• GPM
• Inches of Water Column
• Feet of Water Column
• CFM
• °C
• °F
• Custom
(Custom selection allows for three character spaces to be populated from the 26
alphabet and 13 special characters)
Direct Access Number — F388
Parameter Type —
Numerical
Factory Default —
Application-Specific
Changeable During Run —
Yes
Minimum —
Setting
Maximum —
Setting
Units — Selectable at Wizard
(Virtual Linear Pump) Auto Start-Stop Upper Threshold
Virtual Linear Pump
Auto Start-Stop Threshold Setting
During a properly configured
Virtual Linear Pump
operation while in the
On
Forward
or
On Reverse
modes (
), this parameter establishes the upper
level of the
Auto Start-Stop
threshold.
See
for additional information on this parameter.
The unit of measure for this parameter may be one of the following types — the
type is selected while running the
Virtual Linear Pump Setup Wizard
.
• PSI
• GPM
• Inches of Water Column
• Feet of Water Column
• CFM
• °C
• °F
• Custom
(Custom selection allows for three character spaces to be populated from the 26
alphabet and 13 special characters)
Direct Access Number — F389
Parameter Type —
Numerical
Factory Default —
300.0
Changeable During Run —
Yes
Minimum —
Setting
Maximum —
Setting
Units — Selectable at Wizard